PROFINET Device Parameters


PROFINET device parameters are features that can be selected to set the operating conditions of a device. PROFINET supports 3 types of parameters: Standard parameters, F-parameters, and Dynamic Parameters. The GSD file of each device defines its parameters (GSD files are explained in PROFINET GSD File Basics).

Three Types of Device Parameters

1) Standard Parameters

Standard parameters are available for each device.  The PROFINET Controller configuration tool displays the available parameters and allows the user to make selections. Once the parameters are set they will be stored in the IO controller and downloaded to the device when a connection is established. Some examples of standard parameters include: MRP settings,  send clock, device watchdog time, start-up mode, and device diagnostic selections. Namely, device diagnostic parameters such as wire break, no supply voltage, short circuit, etc.  The following figure on the right shows part of a device parameter selection screen.

2) F-Parameters (Failsafe Parameters)

F-Parameters (Failsafe related parameters) are only available if the device and the controller both support PROFIsafe. Safety parameters are embedded inside the standard parameter packet using the same technique used for PROFIsafe F-IO data embedding (see PROFIsafe Profile Details).  The following table describes F-Parameters in detail.

F-ParameterBlock

Parameter NameByte address Data typeDefinition
F_PRM_Flag10Unsigned8byte field with bits that represent, iPar present, F SIL (Safety Integrity Level) level, F-CRC length
F_PRM_Flag21Unsigned8byte field with bits that represent F-Par Version, iPar present
F_Source_Add2-3Unsigned16Safety address (F-Address) of F-Host
F_Dest_Add4-5Unsigned16Safety address (F-Address) of F-Device
F_WD_Time6-7Unsigned16F-Watchdog time based on a 1ms time base
F_iPar_CRC (optional)8-11Unsigned324 byte CRC for iParameters (if no iPars this field is empty)
F_Par_CRC12-13Unsigned162 byte CRC across the F-Parameter block(and the iPar block if it is present)

3) Dynamic Parameters ( iParameters)

With some field devices, complete parameter assignment through GSD files is not very useful due to the amount of data, the direct user guidance needed, or the specific circumstances in an automation system. Dynamic parameters device or plant-specific data. In most cases, the user must assign these parameters during device commissioning. For example, some safety lasers scanners require a special setup tool to define the protective fields. These field definitions are specific to the location of the scanning device. In case of device replacement, the setup tool is required during recommissioning.

When replacing a field device with dynamic parameters, it would be preferable to automatically reload these parameters into the new field device on voltage recovery rather than recommissioning by hand. PROFINET offers unique support for this type of device with iParameters and the iPar-Server. After the device commissioning a database can store all the dynamic data (iPars) for the future.

iPar-Server

The iPAR-Server is an entity that handles the upload of iPars from the device. It stores them and can restore them to the device upon device replacement. The adjacent figure shows the iPar server operation. By using the iPar-Server to save and automatically upload these dynamic device parameters,  the user avoids additional commissioning time and cost. Although iPars and the iPar server are not requirements for any device, they are features that a vendor can choose to support since they make device replacement easier.

PROFINET Device Parameter Support

In summary, Device GSDML files support the three types of PROFINET device parameters; standard, F-parameters, and Dynamic parameters.  PROFINET Controller programming tools use the GSDML information and allow end users to choose PROFINET device operating details.